Nuisance tripping of residual current devices (RCDs) is an increasingly frequent problem in industry. Factories incorporate more and more electronic devices, most of them fitted with capacitive filters that neutralise the high frequencies generated by their own circuits and stop them from reaching the network.
This has to be taken into account when carrying out the plant’s electrical engineering, because an interruption in the supply can cause serious problems.
Causes and effects of nuisance tripping of RCDs
When we talk about the causes of nuisance tripping of a factory’s RCDs, we have to mention sympathetic tripping, which is common in industry.
What is sympathetic tripping?
It is the simultaneous opening of several RCDs that protect parallel outputs of an installation.
In this type of tripping, horizontal selectivity is lost because of the leakage currents caused by cable capacitance and/or the earthed capacitive filters of electronic loads.
Causes of nuisance tripping
So what exactly causes nuisance tripping in a factory?
There are two common causes. The first is permanent leakage, which depends on the impedance of the capacitances to earth. The second is short transient earth leakage.
The solution?
There are several ways to prevent nuisance tripping. They are based on choosing the right residual current protection devices for each installation and on good design practices such as:
- Limiting the number of electronic loads with earthed capacitive filters under each RCD. Independent lines are a good option for this.
- Whenever there are many electronic devices, considering important aspects such as the type, tripping time and sensitivity of the RCDs.
- Setting the sensitivity to around 10 times the natural leakage level of the circuit.
To improve your plant’s electrical engineering, contact MEINSA and we will help you design the whole project.