The characteristics of the IT earthing system

Earthing arrangements shape the design of an electrical installation and define its nature. Although there are different types, the most recommended for guaranteeing a continuous power supply are IT systems.

IT systems are mainly installed where it is essential to guarantee uninterrupted service. The clearest example is hospitals, particularly operating theatres, where continuity can make the difference between life and death. They are also used for emergency lighting, cold stores, nuclear power plants, oil platforms, public spaces and, of course, industrial processes of various kinds. All these fields need an IT system to ensure a reliable, continuous electricity supply.

When choosing the most suitable earthing arrangement, the characteristics of the sector where it will be used have to be considered, and the electrical design adapted accordingly to protect people, minimise the risk of fire and avoid other incidents. The IT system is the only one that does not interrupt the supply after an insulation fault, but it is an extremely complex arrangement, closely linked to the organisation’s automation systems. This means that both healthcare centres and industrial production lines can keep running even during an incident, because the IT system stays active while having suitable safety measures in place.

Main characteristics of the IT system

First, the position of the letters defines the meaning of the abbreviations used for earthing systems. IT systems are defined by their initials as follows:

  • I: all the live supply components of the system (transformers, generators, etc.) are isolated from earth. Bear in mind, however, that although the transformer neutral is in theory isolated, it is naturally connected to earth through the stray capacitance of the network cables and/or through a high-value impedance (around 1,500 Ω).
  • T: the exposed conductive parts of the system are connected directly to earth.

The earth-isolated IT system has a high impedance between its live parts and earth. The components of the IT system can be earthed individually or collectively, depending on the case.

Because there is no low-impedance live conductor in contact with earth, these systems do not allow a large fault current to flow if a live part touches an exposed conductive part. For this reason, they require an external, independent power source, such as a battery or a generator.

They are also very safe systems: because they are isolated from earth, if someone touches a live conductive part they will only notice a minimal current. Both the fault current and the conductor resistance are very low, so the touch voltages produced are small.

By regulation, IT systems must have an insulation monitoring device. It is connected between the live network conductors and earth, and it detects and warns of a first fault between a live part and an exposed conductive part or earth.

Benefits and advantages of IT electrical systems

IT systems are not the most widely used in electrical design. However, they offer a number of unique advantages that set them apart. Broadly, these are their benefits:

  • Continuity. IT systems guarantee reliable, continuous availability without interruptions. Even if an insulation fault occurs, the system keeps working and supplying all the organisation’s assets. The first fault is reported by the system, but only a second fault will stop it.
  • Monitoring. These systems make it possible to locate insulation faults even while the system is running and in service, so production does not have to be affected. This also removes the need for periodic checks, with the savings that implies.
  • Less damage to components. Because the fault current generated by a first insulation fault is very small, the electrical system suffers very little damage, so its service life is longer than that of TT and TN systems. This reduces repair and maintenance costs.
  • Lower fire risk. The low fault current minimises the risk of fire or explosion, as an electric arc is very unlikely to overheat.
  • Safety. Another advantage of the limited earth fault currents is that the danger is reduced if a person touches exposed live parts directly.

Factors to consider when designing an IT system

Although the IT system has advantages that should be attractive enough, it is not widely used. These are the most common reasons:

  • High cost. Installing an IT system is known to be more expensive than a TN or TT network, but it offers an advantage that pays back the investment. The preventive maintenance associated with IT systems reduces the number of network checks, and with it the time and inspections required. The result is a high initial investment but long-term savings.
  • The need for an insulation fault location system. Unearthed power systems usually require insulation fault location equipment to ensure full, optimal supervision. These devices generate alerts when faults occur in the system.
  • The most outstanding system. Although it is the electrical system with the best characteristics, it is more viable for large, complex electrical networks. A combination of TN, IT and TT systems should not be ruled out either.

Enjoy a stable, continuous electrical network

If your company needs a constant, safe and durable electrical connection, the IT system is the most suitable choice. If you need more information about how this earthing arrangement can be useful in your organisation, just ask us. Our team of specialists in automation and electrical design will help you. Get in touch with us and we will advise you so that you can enjoy all the advantages of these systems.